• + 39 0775/392052 info@digitron-italia.it
  • versione inglese  versione tedesco  versione spagnolo

CO2 and Temperature Transmitter for Duct Mounting

HLX850

The HLX850 is optimized for use in building management applications. A multi-point CO2 and temperature factory adjustment procedure leads to an excellent CO2 measurement accuracy over the entire temperature working range.
The dual wavelength NDIR CO2 sensor compensates for aging effects, is highly insensitive to pollution and offers outstanding long term stability.
The HLX850 can be optionally fitted with a passive temperature sensor output. An optional kit facilitates easy configuration and adjustment.


Key Features
Dual wavelength NDIR CO2 working principle
Measuring range up to 10,000ppm
Auto-calibration for excellent long term stability
Temperature compensation
Highly insensitive to pollution
Voltage or current analogue outputs
Optional passive temperature sensor
Fast and easy installation
Easy user configuration and adjustment

Typical Applications
Building management
Demand controlled ventilation
Process control

TECHN. DATA

Measuring range:

0...2000 / 5000 / 10000ppm

-20...60°C

Outputs:

0...5 / 10V

4...20mA

Accuracy:

0...2000 ppm: ± (50 ppm + 2% of measuring value)

0...5000 ppm: ± (50 ppm + 3% of measuring value)

0...10000 ppm: ± (100 ppm + 5% of measuring value)

Supply:

24V AC/DC

Download Data Sheet Send Mail for information See Measurement CO2