- Ventilation monitoring for energy efficient building
- Evaluate cooling efficiency in the electronic device
- Aerodynamics Research
- Production Control
|
Features
|
- 10 different types of air velocity probes are available for user's application
- Probes are interchangeable, accuracy is steady after changing to spare probe.
- Simultaneously measurement: 4 channel of air velocity.
- RS232C for PC communication
- Analog output
|
Benefits
|
- Probe is interchangeable, accuracy is steady after changing to spare probe.
- Simultaneous measurement: 4 channels of air velocity.
|
Velocità Sonde
|
|
|
Main
Unit Specifications
|
Air
velocity
Resolution
|
0.01
m/s (@
range of 0 to 9.99m/s)
|
0.1
m/s
(@ 10 m/s or more)
|
Data
Output
|
Digital:
RS
232C (Baud rate 9600 bps fixed)
|
Analog:
0 to
5 V
|
Operation
Temperature
|
41
to 104 F
(5 to 40 C)
|
Dimensions
|
D
7.8 x
W 10.2 x H 2.8 inches (200 x 260 x 70 mm)
|
Weight
|
5.7
lbs (2.6
kg)
|
Power
Supply
|
AC
85 to 276
V, 50/60Hz
|
|
|
Probe
Specifications
|
Model
|
Rnage
(m/s)
|
Accuracy
(m/s)
|
Response
Time
|
0962-00
0963-00
|
0.1
to 4.99
|
+/-
0.1
|
1
sec |
5.00
to
9.99
|
+/-
0.2
|
10.0
to
24.9
|
+/-
0.5
|
25.0
to
50.0
|
+/-
1.0
|
0964-01
0964-02
|
0.1
to
4.99
|
+/-
0.15
|
3 sec
|
5.00
to
9.99
|
+/-
0.3
|
10.0
to
24.9
|
+/-
0.75
|
25.0
to
50.0
|
+/-
1.5
|
0965-00/01
0965-03/04
0965-07/08
|
0.1
to
4.99
|
+/-
0.15
|
7 sec
|
5.00
to
9.99
|
+/-
0.3
|
10.0
to
25.0
|
+/-
0.60
|
Temperature
Compensation
|
+/-
5%FS (@ 5 to 40C)
+/- 7%FS (@ 40 to 80C)
|
|